SEC3002 system represents the latest generation of addressable fire alarm control panel designed to comply with the latest versions of EN standard with qualities of simple installation, operation and easy maintenance. The wide range of SEC3002 configurations include standalone operation and networking with up to twenty panels for small to large sized applications.
The A9056T I/O module is used with an intelligent two-bus linkage fire alarm control system.It is mainly used to realize an output control for fire linkage equipment (such as smoke dampers, blow valves and fire dampers) and receive the feedback signals of the fire linkage equipment so that a judgment on whether or not the fire linkage equipment is operating normally can be done.
Semi-flush or surface mount
Lever reusable (non-glass break)
LED indicator
Full soft addressing, and rewriting through CODER-9001 encoder in site. Comply with EN54-18
1. Mode of operation: Nonpolar two-wire system
2. Quiescent current: <0.6mA; Action current: <10mA
3. Capacity of the output control contact: <2A@DC30V
4. Operating environment: Temperature: - 10ºC ~ 55ºC ; relative humidity: ≤95% (40ºC ±2ºC , without condensation)
5. Operation indicator: The inspection indicator will blink once about every 12 seconds in the inspection status or remain lit in the output status; the input indicator will remain lit in the feedback status.
6. External dimensions: 86×86×40(mm)
7. Weight: about 140g(With base)
8. Executive standard: EN54-18