SEC3002 system represents the latest generation of addressable fire alarm control panel designed to comply with the latest versions of EN standard with qualities of simple installation, operation and easy maintenance. The wide range of SEC3002 configurations include standalone operation and networking with up to twenty panels for small to large sized applications.
The A9060T manual call point(hereinafter referred to A9060T) is mainly designed to be used with an intelligent two-bus control system. If it is pressed after a fire is manually confirmed, an alarm signal may be sent to a fire alarm control system which will, after receiving the alarm signal, display the coded address and the equipment status of the manual fire call points. When the manual fire call points is operating normally, the red indicator will blink; when there is a fire alarm, it will remain lit. The A9060T supports electronic coding, more suitable for engineering application convenient.
Semi-flush or surface mount
Lever reusable(non-glass break)
LED indicator
Support non-polarity,complete soft addressing in situ
Desianed with passive output contacts to control other external equipmentdirectly via an intermediate relay
Comply with EN54-11
1.Executive Standard:EN54-11
2.Protection class:IP43
3.Operating voltage:24V (pulse modulation)
4.Operating Current:monitoring status <300uA, alarm status <2mA
5.Application:For indoor use
6.Operating temperature: -10 ºC ~ 55 ºC,Relative humidity:≤ 95% (non-condensing)
7.Indicator:Red alarm indicator flashes when data logging, press the manual button lit work
8.Encoding:coded by the encoder, the address range from 1 to 324 optional
9.Materials and colors:ABS, red
10.Wiring:The Promise of two bus system (L1, L2)
11.Size : 90mm × 90mm × 42mm (overall height) / 90mm × 90mm × 23mm (exposed after installation dimensions)
12.Mating Host:SEC3002 fire alarm control panel
13.Weight:about 95g